Cover Core ONE 2K UPS Uninterruptible Power Supply

Add to compare
Indeks:
COVER-CORE-2K

The COVER-CORE-2K UPS is equipped with advanced power grid monitoring technologies. The device is installed in a 19" rack. It is an online power supply that provides effective protection against fluctuating power grid parameters. It operates safely, completely isolating connected devices and offering protection against unexpected power outages. This model supplies battery power and ensures uninterrupted power to devices while simultaneously recharging the batteries in the background.

  • Backup time for 100% load 4 minutes Backup time for 50% load 11 minutes Apparent power 2000 VA Effective power 2000 W Tower housing
1,898.00 zł (Tax Incl.)
1,543.09 zł (Tax Excl.)
Delivery from: 0.00 zł
Details
Shipping: 3 December (Thu.)
Product available from the supplier
24-hour service
Over 20 years of experience
Up to 5 years warranty
1,898.00 zł (Tax Incl.)
1,543.09 zł (Tax Excl.)
1,898.00 zł (Tax Incl.)
1,543.09 zł (Tax Excl.)

Description

UPS CORE ONE 2 kVA - True On-Line Rack/Tower 2U, PF = 1.0

The CORE ONE 2K UPS is a professional True On-Line Double Conversion (VFI-SS-111) 2 kVA/2 kW power supply with a 2U Rack/Tower chassis. It provides the highest voltage quality, operational stability, and complete protection for sensitive loads in IT, automation, and security systems.

Why choose CORE ONE?

  • True On-Line Technology (VFI-SS-111) – excellent output parameters regardless of interference; automatic bypass (Static Switch) guarantees power continuity in critical situations.

  • Power factor PF = 1.0 – up to 30% more active power than typical UPSs of this class.

  • High efficiency – up to ≥93% in On-Line mode and 99% in ECO , which actually reduces energy consumption and cooling costs.

  • CVCF (50/60 Hz) – works as a frequency converter for non-standard receivers.

  • Wide input voltage range – batteries are only used when necessary; input PF ≥0.99, THDi <3% .

  • Programmable socket groups – possibility of remote, sequential shutdown during battery operation.

  • Full communication and security – USB, RS232, TVSS, SNMP Slot, REPO ; optional AS-400, Dry Contact, RS485/Modbus .

  • 2U Rack/Tower + LCD panel – space saving and quick diagnostics; <48 dB – quiet operation in the office and server room.

  • Flexible autonomy – powerful charging system, external battery modules and 3-stage charging to extend battery life.

Applications

Servers and workstations, 19” racks, networks and telecommunications, CCTV and access control systems, laboratory equipment, automation and control, lighting and small data centers.

CORE ONE 2K Specifications at a Glance

  • Topology/Class: True On-Line Double Conversion/ VFI-SS-111 (EN 62040-3) .

  • Power and PF: 2 kVA = 2 kW , output PF 1.0 ; input PF ≥0.99 .

  • Phases/format: 1:1 , 2U Rack/Tower (rotatable LCD panel).

  • Input: 200/208/220/230/240 VAC; wide voltage range (up to −52%…+30% depending on load); THDi <3% .

  • Output: 200/208/220/230/240 VAC; THDu <2% , regulation ±1%/±3%; 50/60 Hz ±0.05 Hz .

  • Inverter overload capacity: 110% – no limit; 130% – 5 min; 140% – 30 s; >140% – 1.5 s.

  • Sockets: 8× IEC C13 ;

  • Batteries (internal): 4×9 Ah; battery start , external battery connection (time to 90%: approx. 4 h).

  • Autonomy (internal/ +1 module): approx. 4/20–21 min (100%) , 6–7/28 min (75%) , 11–12/46–51 min (50%) depending on the model.

  • Noise <48 dB .
  • Communication: USB, RS232, TVSS, SNMP Slot, REPO ; options: SNMP, AS-400, Dry Contact, RS485 (Modbus) .

  • Standards: EN 62040-1:2019, EN 62040-3:2022, EN 62040-2:2018; CE/UKCA, RoHS.

How is CORE ONE different from Line-Interactive?
CORE ONE is True On-Line – the power supply generates voltage with constant parameters regardless of the mains; additionally, it has CVCF and automatic bypass .

Can I extend the backup time?
Yes – external battery modules are available and the powerful charging system supports large battery capacities.

Specification

Power factor
PF 0.99
Phase configuration
1-1 (Plug & Play)
Frequency
50/60 Hz
Rated power kVA
2 kVA
Supply voltage
200 / 208 / 220 / 230 / 240 VAC
Voltage range
-30% ÷ +30% -100% load - 50% -52% ÷ +30% - 50% load. - 0%
Frequency range
-20% ÷ +20%
THDi
less than 3%
Static/dynamic voltage regulation
±1% / ±3%

Reviews