UPS Cover 3-phase PS 20K emergency power supply
UPS PS 20 kVA - True On-Line VFI, Rack/Tower 3U, PF = 1.0
The PS 20 kVA UPS series is a powerful True On-Line Double Conversion power supply (VFI-SS-111) with high efficiency and a compact 3U chassis – designed to protect server rooms, telcos, and automation systems in 24/7 operation. With an output PF of 1.0 and an input PF of ≥0.99, they ensure full power utilization even with low system load.
Why choose the PS 20K series?
Reliability of the VFI + Static Switch class (uninterruptible bypass) – constant, pure sinusoidal voltage regardless of interference and continuity of power supply in critical situations.
Flexible phase configuration – PS 20K supports 1:1, 3:1, 3:3, and even 1:3. Easily fit the UPS into your existing distribution board.
Split Bypass – separate power supply for the rectifier and bypass circuits increases reliability and facilitates cascade operation.
IGBT rectifier + 3-level IGBT inverter (PWM) – very low distortion ( THDi <3% ), stable output voltage and high energy efficiency.
High efficiency – up to 96% in On-Line mode and 98% in ECO-Mode to minimize energy and cooling costs.
Wide input window 100–300 V [LN] / 278–522 V [LL] and 45–65 Hz – stable operation in unstable networks and with a generator.
N+1 parallel operation (up to 3 units) – power scaling or redundancy for key systems.
Full communication and security – USB, RS232, SNMP, REPO , LCD + LED panel with event log and wide parameter configuration.
Advanced battery management + Battery start – longer life and the ability to start the UPS even in the absence of mains power.
Compact 19″ Rack / Tower (3U) installation – easy integration in server racks and technical rooms.
Applications
Computer networks and servers • 19″ racks • Telecommunications • Laboratory equipment • Automation and control • Small/medium data centers.
Key parameters of PS 20K
Power and PF: 20 kVA = 20 kW, PF output 1.0.
Phases: PS 20K: 1:1, 3:1, 3:3, 1:3 .
Input: [LN] 100–300 VAC (load dependent), [LL] 278–522 VAC (100% load); 45–65 Hz ; THDi <3% ; PF ≥0.99 .
Output: [LN] 220/230/240 VAC • [LL] 380/400/415 VAC; regulation ±1% / ±3% (stat./dynam.); 50/60 Hz ±0.1 Hz ; CF 3:1 .
Overload capacity: 105% – no limit, 125% – 10 min, 150% – 30 s, >150% – 500 ms .
Efficiency: 96% On-Line , 98% ECO-Mode .
Batteries: 32–40 × 12 V ; charging current 1–13 A ; 3–8 h to 90% (configurable); optional temperature compensation. Note: each UPS requires at least 2 battery modules ( 6U total).
Dimensions / weight UPS: 3U, 440 × 680 × 132 mm ; 32 kg . Battery module 3U (20 batteries): 440 × 780 × 132 mm / 65 kg .
Environment/Noise: Operating 0–40 °C ( 15–25 °C recommended), Humidity 0–95% (non-condensing), <65 dB @100% load
Standards and options: EN 62040-1:2019 , EN 62040-2:2018 , CE; optional SNMP , external maintenance bypass, rack/frame battery modules, REPO .
What do IT and maintenance departments gain?
Higher availability – Split Bypass + N+1 parallel operation.
Lower OPEX – high efficiency over a wide load range, less heat and longer battery life.
Simple integration and operation – 3U/Tower rack, rich telemetry (USB/RS232/SNMP/REPO) and intuitive LCD with event log.
- Power factor
- PF 0.99
- Phase configuration
- 1-1, 3-1, 3-3, 1-3,
- Frequency
- 50/60 Hz
- Rated power kVA
- 20 kVA
- Supply voltage
- 220 / 230 / 240 VAC
- Voltage range
- 100 ÷ 160 VAC linear for load 50% - 100%, 160 ÷ 300 VAC for load 100%
- Frequency range
- 45 ÷ 65 Hz
- THDi
- less than 3%
- Static/dynamic voltage regulation
- ±1% / ±3%
- Efficiency in On-Line Mode
- 96%