UPS Cover 3-phase FRAME 120K uninterruptible power supply

Add to compare
Indeks:
COVER-FRAME-120K

The Cover FRAME 120K 3-phase emergency power supply is an advanced power backup system featuring a TRUE ON-LINE topology with a capacity of 120kW = 120 kVA. This system delivers clean electricity and protects connected devices from all common grid issues. Equipped with a three - level inverter topology , it ensures high efficiency, reaching 96% in online mode and up to 99% in ECO mode. Designed to work with external EBM battery cabinets.

40,190.99 zł (Tax Incl.)
32,675.60 zł (Tax Excl.)
Delivery from: 0.00 zł
Details
Shipping: 7 December (Mon.)
Product available from the supplier
24-hour service
Over 20 years of experience
Up to 5 years warranty
40,190.99 zł (Tax Incl.)
32,675.60 zł (Tax Excl.)
40,190.99 zł (Tax Incl.)
32,675.60 zł (Tax Excl.)

Description

UPS FRAME 120 kVA - modular True On-Line 3:3, PF = 1.0, Hot-Swap

The FRAME 120K UPS series is a three-phase, modular, True On-Line Double Conversion power supply (VFI-SS-111) designed to provide uninterrupted power to critical IT, industrial, and telecommunications infrastructure. Hot-swap architecture and parallel operation with redundancy improve availability, while 1.0 output power factor and >96% efficiency (ECO 99%) significantly reduce energy and cooling costs.

Why choose UPS Cover FRAME 120K?

  • Modular design with Hot-Swap – quick replacement of power modules without shutting down the system; easy power scaling and redundant configurations ( N+1 , capacitive, Hot-Standby ).

  • VFI class reliability – pure sine wave regardless of interference; automatic bypass (uninterruptible) and service bypass with a separate track for maintenance work without downtime.

  • IGBT + 3-level inverter (PWM) – very low distortion ( THDi <3% , THDu low ), high efficiency; input PF ≥0.99 , output PF 1.0 .

  • Wide input window – 304–485 V for 100% load; up to 138–304 V linear for 40–100% load; 40–70 Hz – stable operation also with a generator.

  • Advanced management – USB, RS232, RS485, Dry Contact, NET/SNMP (optional) , EPO ; 5.0″ color touch panel with event log and full diagnostics.

  • Hibernation of modules in parallel operation – dynamic adjustment of the number of active modules to the load (less heat and noise).

  • Conformal coating + redundant fans – increased environmental resistance and continuous operation even in the event of fan failure.

Applications

Data centers and server rooms • Computer networks and telecommunications • Industrial lines and equipment • Laboratory equipment • Building automation and process control.

Specifications at a glance Cover FRAME 120 kVA

  • Topology / Class: True On-Line Double Conversion / VFI-SS-111 (EN 62040-3) | Phase Configuration: 3:3 .

  • 120 kVA model / power modules: 3 ×40 kW .

  • Input: 380/400/415 VAC; 304–485 VAC (100% load) , min. 138–304 VAC linear for 40–100% load; 40–70 Hz ; THDi <3% ; PF ≥0.99 .

  • Output: 380/400/415 VAC; PF 1.0 ; regulation ±1% / ±2% (stat./dyn.); 50/60 Hz ±0.05 Hz ; CF 3:1 ; overload capacity 105–110%: 60 min; 110–125%: 10 min; 125–150%: 1 min; >150%: 0.2 s .

  • Efficiency: >96% On-Line , ECO 99% ; Soft Start as standard.

  • Batteries: VRLA/AGM/GEL/Ni-Cd/Li-Ion; 32–44×12 V in string; 36 A chargers ; 3–8 h to 90% , temperature compensated. Battery start (cold start).

  • Control and I/O: USB, RS232, RS485, NET, EPO, LBS, dry-contact , parallel operation connectors; options: SNMP, GPRS, Wi-Fi, battery probe .

  • Dimensions / weight (without batteries):

    • 120 kVA: 440×850×1200 mm / 198 kg

  • Environment: IP20 , <65 dB , operating 0–40 °C ( 15–25 °C recommended), humidity 0–95% non-condensing

  • Standards / Installation Options: EN 62040-1:2019 , EN 62040-2:2018 , EN 62040-3:2011 , CE/UKCA ; Options: External Uninterruptible/Maintenance Bypass , BackFeed Protection , Rack Batteries or Battery Modules, Parallel Cables.

Advantages for the IT and maintenance department

  • Scalability without downtime (Hot-Swap) and OPEX reduction thanks to high efficiency and 99% ECO-Mode .

  • Advanced telemetry (SNMP/BMS) + 5″ panel with event log – quick diagnostics and precise configuration.

  • Environmental resistance (conformal coating) and redundant fans – higher availability in real operating conditions.

Specification

Power factor
PF 0.99
Phase configuration
3-3
Frequency
50/60 Hz
Rated power kVA
120 kVA
Supply voltage
380 / 400 / 415 VAC
Voltage range
304 VAC - 485 VAC for 100% load. Min. 138 VAC - 304 VAC linear for 40% - 100% load
Frequency range
40 ÷ 70 Hz
THDi
less than 3%
Static/dynamic voltage regulation
±1% / ±2%
Efficiency in On-Line Mode
over 96%

Attachments

Comex FRAME 120K Catalog Card

Download (359.61KB)

Reviews

Find out what our customers say about us
No customer reviews for the moment.
Loading...