UPS Cover 3-phase FRAME 120K uninterruptible power supply
UPS FRAME 120 kVA - modular True On-Line 3:3, PF = 1.0, Hot-Swap
The FRAME 120K UPS series is a three-phase, modular, True On-Line Double Conversion power supply (VFI-SS-111) designed to provide uninterrupted power to critical IT, industrial, and telecommunications infrastructure. Hot-swap architecture and parallel operation with redundancy improve availability, while 1.0 output power factor and >96% efficiency (ECO 99%) significantly reduce energy and cooling costs.
Why choose UPS Cover FRAME 120K?
Modular design with Hot-Swap – quick replacement of power modules without shutting down the system; easy power scaling and redundant configurations ( N+1 , capacitive, Hot-Standby ).
VFI class reliability – pure sine wave regardless of interference; automatic bypass (uninterruptible) and service bypass with a separate track for maintenance work without downtime.
IGBT + 3-level inverter (PWM) – very low distortion ( THDi <3% , THDu low ), high efficiency; input PF ≥0.99 , output PF 1.0 .
Wide input window – 304–485 V for 100% load; up to 138–304 V linear for 40–100% load; 40–70 Hz – stable operation also with a generator.
Advanced management – USB, RS232, RS485, Dry Contact, NET/SNMP (optional) , EPO ; 5.0″ color touch panel with event log and full diagnostics.
Hibernation of modules in parallel operation – dynamic adjustment of the number of active modules to the load (less heat and noise).
Conformal coating + redundant fans – increased environmental resistance and continuous operation even in the event of fan failure.
Applications
Data centers and server rooms • Computer networks and telecommunications • Industrial lines and equipment • Laboratory equipment • Building automation and process control.
Specifications at a glance Cover FRAME 120 kVA
Topology / Class: True On-Line Double Conversion / VFI-SS-111 (EN 62040-3) | Phase Configuration: 3:3 .
120 kVA model / power modules: 3 ×40 kW .
Input: 380/400/415 VAC; 304–485 VAC (100% load) , min. 138–304 VAC linear for 40–100% load; 40–70 Hz ; THDi <3% ; PF ≥0.99 .
Output: 380/400/415 VAC; PF 1.0 ; regulation ±1% / ±2% (stat./dyn.); 50/60 Hz ±0.05 Hz ; CF 3:1 ; overload capacity 105–110%: 60 min; 110–125%: 10 min; 125–150%: 1 min; >150%: 0.2 s .
Efficiency: >96% On-Line , ECO 99% ; Soft Start as standard.
Batteries: VRLA/AGM/GEL/Ni-Cd/Li-Ion; 32–44×12 V in string; 36 A chargers ; 3–8 h to 90% , temperature compensated. Battery start (cold start).
Control and I/O: USB, RS232, RS485, NET, EPO, LBS, dry-contact , parallel operation connectors; options: SNMP, GPRS, Wi-Fi, battery probe .
Dimensions / weight (without batteries):
120 kVA: 440×850×1200 mm / 198 kg
Environment: IP20 , <65 dB , operating 0–40 °C ( 15–25 °C recommended), humidity 0–95% non-condensing
Standards / Installation Options: EN 62040-1:2019 , EN 62040-2:2018 , EN 62040-3:2011 , CE/UKCA ; Options: External Uninterruptible/Maintenance Bypass , BackFeed Protection , Rack Batteries or Battery Modules, Parallel Cables.
Advantages for the IT and maintenance department
Scalability without downtime (Hot-Swap) and OPEX reduction thanks to high efficiency and 99% ECO-Mode .
Advanced telemetry (SNMP/BMS) + 5″ panel with event log – quick diagnostics and precise configuration.
Environmental resistance (conformal coating) and redundant fans – higher availability in real operating conditions.
- Power factor
- PF 0.99
- Phase configuration
- 3-3
- Frequency
- 50/60 Hz
- Rated power kVA
- 120 kVA
- Supply voltage
- 380 / 400 / 415 VAC
- Voltage range
- 304 VAC - 485 VAC for 100% load. Min. 138 VAC - 304 VAC linear for 40% - 100% load
- Frequency range
- 40 ÷ 70 Hz
- THDi
- less than 3%
- Static/dynamic voltage regulation
- ±1% / ±2%
- Efficiency in On-Line Mode
- over 96%