AP 150 P three-phase generator – compact Perkins power for your business
What is the AP 150 P generator?
The AP 150 P is a compact yet efficient three-phase generator with a maximum output of 150 kVA / 120 kW , designed for emergency or primary power in medium-sized companies, workshops, manufacturing plants, and service facilities. Equipped with a reliable Perkins 1106A-70TG1 engine, it complies with the 97/68/EC exhaust emissions directive.
What are the key technical parameters of the AP 150 P generator?
-
ESP maximum power: 150 kVA / 120 kW
-
PRP rated power: 135 kVA / 108 kW
-
Rated current: 195 A
-
Nominal voltage: 400/230 V
-
Frequency: 50 Hz
-
Generator: STRATHON ECO 150 KW, brushless, synchronous
-
Generator efficiency: 93%
-
Degree of protection: IP 23
-
Insulation class: H
Why choose the AP 150 P generator?
What makes the AP 150 P stand out?
✅ Perkins 1106A-70TG1 engine: 6-cylinder in-line, capacity 7.01 l, power 136.9 kW, electronic speed controller – guarantee of stable operation even under variable load.
✅ AMF 20 controller: Intuitive graphical interface, automatic start-up, current and voltage measurement in 3 phases, event log (up to 119 entries), energy meter, online monitoring (GSM, LAN, Modbus).
✅ Economical combustion: Fuel consumption at 100% load is only 22.7 l/h , and the 200 l fuel tank allows for long, uninterrupted operation.
✅ Quiet operation: Soundproof housing – the noise level is only 70 dB(A) at a distance of 7 m.
Where is the AP 150 P generator best suited?
AP 150 P is a reliable energy source for:
-
medium-sized production plants and workshops,
-
service points and shops,
-
offices and administrative facilities,
-
health care facilities and medical facilities,
-
places where compliance with exhaust emission standards is required.
What additional options does the AP 150 P unit offer?
You can expand the unit with:
-
external fuel tank,
-
synchronization with other units,
-
ventilation and exhaust system,
-
spark arrester,
-
differential protection,
-
remote monitoring (GSM, LAN),
-
execution in a different voltage version,
-
external SZR cabinet (IP54),
-
foundation slab.
What is the service and operation of AP 150 P generators like?
How to take care of the generator?
? Oil and filter change: after the first 100 hours of operation, then every 500 hours or every year.
? Coolant: replace every 1000 hours or every 2 years.
? AMF 20 Controller: enables remote monitoring, SMS/email notifications, InteliMonitor and WebSupervisor.
What are the warranty conditions for the AP 150 P?
-
Reserve mode: 60 months (or 1000 operating hours), provided required maintenance is performed.
-
Continuous operation mode: 12 months (or 1000 operating hours).
Choose reliable power supply with AP 150 P
The AP 150 P offers the certainty of constant current, quiet operation and compliance with emission standards – where there is no room for compromise.
Contact us and request an offer tailored to your needs!
- Execution
- Built-up
- Maximum power ESP kVA
- 150 kVA
- Maximum power ESP kW
- 120 kW
- Rated power PRP kVA
- 135 kVA
- Rated power PRP kW
- 108 kW
- Rated current
- 195 A
- Tension
- 400V
- Frequency
- 50 Hz
- Engine
- Perkins
- Fuel type
- Diesel
- Fuel consumption 100% l/h
- 22.7 l/h
- Fuel tank
- 200 l
- Dimensions L x W x H
- 2890 x 1110 x 1750 mm
- Application
-
Business
Construction
Data Center
Health service
Industry