AP 1230 P three-phase generator – power and reliability with a Perkins engine
What is the AP 1230 P generator?
The AP 1230 P is a three-phase generator with a maximum output of 1230 kVA / 984 kW , designed for emergency and continuous operation in large industrial plants, logistics centers, healthcare facilities, and infrastructure investments. Equipped with a powerful Perkins 4008-30TAG3 engine, it complies with the 97/68/EC exhaust emissions directive.
What are the key technical parameters of the AP 1230 P generator?
-
ESP maximum power: 1230 kVA / 984 kW
-
PRP rated power: 1107 kVA / 885 kW
-
Rated current: 1605 A
-
Nominal voltage: 400 V
-
Frequency: 50 Hz
-
Generator: STRATHON ECO 1250 KW, brushless, synchronous
-
Generator efficiency: 93%
-
Protection class: IP 23
-
Insulation class: H
Why choose the AP 1230 P generator?
What makes the AP 1230 P stand out?
✅ Perkins 4008-30TAG3 engine: 8-cylinder in-line, capacity 30.56 l, power 1055 kW, electronic speed controller – guarantee of stable operation even under heavy loads.
✅ Modern AMF 20 controller: Automatic start-up, current and voltage measurement in 3 phases, event log with up to 119 entries, energy meter, online monitoring (GSM, LAN, Modbus).
✅ Large fuel tank: 1500 l , which with a consumption of 188 l/h at 100% load ensures many hours of work without refueling.
✅ Quiet operation: Soundproof housing – noise level only 70 dB(A) at a distance of 7 m, despite high power.
Where is the AP 1230 P generator best suited?
AP 1230 P is a reliable energy source for:
-
large industrial plants and production halls,
-
data and logistics centers,
-
health care facilities and hospitals,
-
renewable energy farms and infrastructure investments,
-
places where constant, high power and compliance with emission standards are required.
What additional options does the AP 1230 P unit offer?
You can expand the unit with:
-
external fuel tank,
-
synchronization with other units,
-
ventilation and exhaust system,
-
spark arrester,
-
differential protection,
-
remote monitoring (GSM, LAN),
-
execution in a different voltage configuration,
-
external SZR cabinet (IP54),
-
foundation slab.
What is the service and operation of AP 1230 P generators like?
How to take care of the generator?
? Oil and filter change: after the first 100 hours, then every 500 hours or every year.
? Coolant: replace every 1000 hours or every 2 years.
? AMF 20 Controller: enables online monitoring, SMS/email notifications and operation via InteliMonitor and WebSupervisor.
What are the warranty conditions for the AP 1230 P?
-
Reserve mode: 60 months (or 1000 operating hours), provided required maintenance is performed.
-
Continuous operation mode: 12 months (or 1000 operating hours).
Choose stable power with AP 1230 P
The AP 1230 P guarantees reliable power supply, quiet operation and compliance with emission standards – where electricity is crucial.
Contact us and request an offer tailored to your needs!
- Execution
- Built-up
- Maximum power ESP kVA
- 1230 kVA
- Maximum power ESP kW
- 984 kW
- Rated power PRP kVA
- 1107 kVA
- Rated power PRP kW
- 885 kW
- Rated current
- 1605 A
- Tension
- 400V
- Frequency
- 50 Hz
- Engine
- Perkins
- Fuel type
- Diesel
- Fuel consumption 100% l/h
- 188 l/h
- Fuel tank
- 1500 l
- Dimensions L x W x H
- 6000 x 2400 x 3000 mm
- Application
-
Business
Data Center
Health service
Industry - Weight
- 11700 kg