AP 1500 P three-phase generator – powerful and reliable Perkins
What is the AP 1500 P generator?
The AP 1500 P is a powerful three-phase generator with a maximum output of 1500 kVA / 1200 kW , designed for emergency or continuous power in large industrial plants, data centers, hospitals, and strategic investments. Equipped with a Perkins 4012-46TWG3A engine, it meets the requirements of the 97/68/EC exhaust emissions directive.
What are the key technical parameters of the AP 1500 P generator?
-
ESP maximum power: 1500 kVA / 1200 kW
-
PRP rated power: 1350 kVA / 1080 kW
-
Rated current: 1957 A
-
Nominal voltage: 400 V
-
Frequency: 50 Hz
-
Generator: STRATHON ECO 1500 KW, brushless, synchronous
-
Generator efficiency: 93%
-
Protection class: IP 23
-
Insulation class: H
Why choose the AP 1500 P generator?
What makes the AP 1500 P stand out?
✅ Perkins 4012-46TWG3A engine: 12-cylinder V-twin, capacity 45.84 l, power 1224 kW, electronic speed controller – stable operation even under heavy load.
✅ AMF 20 controller: Automatic start-up, current and voltage measurement in 3 phases, event log (up to 119 items), energy meter, online monitoring (GSM, LAN, Modbus).
✅ Large fuel tank: 2000 l – ensures long operation without the need to refuel, even under full load.
✅ Quiet operation: Silent housing – noise level only 70 dB(A) at a distance of 7 m, which is impressive considering its high power.
Where is the AP 1500 P generator best suited?
AP 1500 P is a reliable energy source for:
-
large industrial plants and production halls,
-
data centers and healthcare facilities,
-
logistics centers and warehouses,
-
construction and infrastructure investments,
-
places where compliance with emission standards and constant high power are required.
What additional options does the AP 1500 P unit offer?
You can expand the unit with:
-
external fuel tank,
-
synchronization with other units,
-
ventilation and exhaust system,
-
spark arrester,
-
differential protection,
-
remote monitoring (GSM, LAN),
-
available in a different voltage version,
-
external SZR cabinet (IP54),
-
foundation slab.
What is the service and operation of AP 1500 P generators like?
How to take care of the generator?
? Oil and filter change: after the first 100 hours, then every 500 hours or every year.
? Coolant: replace every 1000 hours or every 2 years.
? AMF 20 Controller: allows remote monitoring, SMS/email notifications and operation via InteliMonitor and WebSupervisor.
What are the warranty conditions for the AP 1500 P?
-
Reserve mode: 60 months (or 1000 operating hours), with required maintenance performed.
-
Continuous operation mode: 12 months (or 1000 operating hours).
Choose maximum power and safety with the AP 1500 P
The AP 1500 P guarantees stable power supply, quiet operation and compliance with emission standards – where electricity must be available at all times.
Contact us and request an offer tailored to your needs!
- Execution
- Built-up
- Maximum power ESP kVA
- 1500 kVA
- Maximum power ESP kW
- 1200 kW
- Rated power PRP kVA
- 1350 kVA
- Rated power PRP kW
- 1080 kW
- Rated current
- 1957 A
- Tension
- 400V
- Frequency
- 50 Hz
- Engine
- Perkins
- Fuel type
- Diesel
- Fuel tank
- 2000 l
- Dimensions L x W x H
- 6000 x 2400 x 3000 mm
- Application
-
Business
Data Center
Health service
Industry - Weight
- 14200 kg