FD 455 SC three-phase generator – reliable Scania power for special tasks
What is the FD 455 SC generator?
The FD 455 SC is a modern three-phase generator with a maximum output of 500 kVA / 400 kW , designed for emergency or continuous operation in large industrial plants, logistics centers, hospitals, renewable energy farms, and infrastructure facilities. Equipped with a Scania DC13 072A 02-13 engine, it meets emission standards in accordance with Directive 97/68/EC.
What are the key technical parameters of the FD 455 SC generator?
-
ESP maximum power: 500 kVA / 400 kW
-
PRP rated power: 455 kVA / 364 kW
-
Rated current: 657 A
-
Nominal voltage: 400 V
-
Frequency: 50 Hz
-
Generator: Leroy Somer, brushless, synchronous
-
AVR type: digital
-
Protection class: IP 23
-
Insulation class: H
-
Reactance Xd: 10.6%
-
Voltage stabilization: ±0.25%
Why choose the FD 455 SC generator?
What makes the FD 455 SC stand out?
✅ Scania DC13 072A 02-13 engine: 6-cylinder, in-line, capacity 12.7 l, power 393 kW, electronic speed governor – stable operation under heavy load.
✅ AMF 25 controller: Intuitive graphical interface, automatic start, current and voltage measurement in 3 phases, event log (up to 119 entries!), energy meter, online monitoring (GSM, LAN, Modbus).
✅ Efficient combustion: Fuel consumption at 100% load is 87.8 l/h , and the 990 l fuel tank allows for many hours of uninterrupted operation.
✅ Quiet operation: In a sound-proof housing, the sound pressure level is only ~69 dB(A) at a distance of 7 m.
Where is the FD 455 SC power generator best suited?
FD 455 SC is a reliable energy source for:
-
large industrial and manufacturing plants,
-
logistics centers and warehouses,
-
renewable energy farms and infrastructure installations,
-
hospitals and health care facilities,
-
investments where continuity of power supply is key.
What additional options does the FD 455 SC adapter offer?
You can expand the unit with:
-
external fuel tank,
-
synchronization with other units,
-
ventilation and exhaust system,
-
spark arrester,
-
differential protection,
-
remote monitoring (GSM, LAN, Modbus),
-
execution in a different voltage configuration,
-
external SZR cabinet (IP54),
-
foundation slab.
What is the service and operation of FD 455 SC generators like?
How to take care of the generator?
? Oil and filter change: after the first 100 hours of operation, then every 500 hours or once a year (oil pan: 36 l).
? Coolant: replace every 1000 hours or every 2 years (capacity: 38 l).
? AMF 25 Controller: enables online monitoring, SMS/email notifications, InteliMonitor and WebSupervisor.
What are the warranty conditions for the FD 455 SC?
-
Reserve mode: 60 months (or 1000 operating hours), provided periodic inspections are performed.
-
Continuous operation mode: 12 months (or 1000 operating hours).
Choose reliable power with the FD 455 SC
The FD 455 SC offers high power, safety and compliance with emission standards – wherever electricity must be available at all times.
Contact us and request an offer tailored to your needs!
- Execution
- Built-up
- Maximum power ESP kVA
- 500 kVA
- Maximum power ESP kW
- 400 kW
- Rated power PRP kVA
- 455 kVA
- Rated power PRP kW
- 364 kW
- Rated current
- 657 A
- Tension
- 400V
- Frequency
- 50 Hz
- Engine
- Scania
- Fuel type
- Diesel
- Fuel consumption 100% l/h
- 87.8 l/h
- Fuel tank
- 990 l
- Dimensions L x W x H
- 4900 x 1530 x 2500 mm
- Application
-
Business
Data Center
Industry - Weight
- 4130 kg