AP 715 B three-phase generator – a reliable source of high power from Baudouin
What is the AP 715 B generator?
The AP 715 B is an efficient three-phase generator with a maximum output of 715 kVA / 572 kW , designed for emergency and primary operation in large industrial plants, logistics centers, healthcare facilities, and infrastructure investments. Equipped with a robust Baudouin 6M33G715 engine, it meets the requirements of the 97/68/EC exhaust emissions directive.
What are the key technical parameters of the AP 715 B generator?
-
ESP maximum power: 715 kVA / 572 kW
-
PRP rated power: 643 kVA / 515 kW
-
Rated current: 932 A
-
Nominal voltage: 400 V
-
Frequency: 50 Hz
-
Generator: STRATHON ECO 750 KW, brushless, synchronous
-
AVR Type: DVR, Digital
-
Protection class: IP 23
-
Insulation class: H
-
Generator efficiency: 93%
Why choose the AP 715 B generator?
What makes the AP 715 B special?
✅ Baudouin 6M33G715 engine: 6-cylinder in-line, capacity 19.6 l, power 633 kW, electronic speed controller – stable operating parameters under variable load.
✅ AMF 25 controller: Intuitive graphical interface, automatic start, current and voltage measurement in 3 phases, event log (up to 119 entries), energy meter, online monitoring (GSM, LAN, Modbus).
✅ Capacious fuel tank: 800 l , which with a consumption of 136.3 l/h at 100% load allows for many hours of uninterrupted work.
✅ Quiet operation: Silenced housing – the noise level is only 70 dB(A) at a distance of 7 m, which is an excellent result for such power.
Where is the AP 715 B power generator best suited?
AP 715 B is a reliable energy source for:
-
large industrial plants and production halls,
-
logistics centers and warehouses,
-
hospitals and health care facilities,
-
renewable energy farms and large construction investments,
-
places where high power parameters and compliance with emission standards are required.
What additional options does the AP 715 B unit offer?
You can expand the unit with:
-
external fuel tank,
-
synchronization with other units,
-
spark arrester,
-
ventilation and exhaust system,
-
differential protection,
-
remote monitoring (GSM, LAN),
-
execution in a different voltage configuration,
-
external SZR cabinet (IP54),
-
foundation slab.
What is the service and operation of AP 715 B generators like?
How to take care of the generator?
? Oil and filter change: after the first 100 hours of operation, then every 500 hours or every year.
? Coolant: replacement every 1000 hours or every 2 years (system capacity: 159 l).
? AMF 25 Controller: enables remote monitoring, SMS/email notifications, InteliMonitor and WebSupervisor.
What are the warranty conditions for the AP 715 B?
-
Reserve mode: 60 months (or 1000 operating hours) – when performing periodic inspections.
-
Continuous operation mode: 12 months (or 1000 operating hours).
Choose reliable power supply with the AP 715 B
The AP 715 B offers reliable power, quiet operation and full compliance with emission requirements – where electricity is critical.
Contact us and request an offer tailored to your needs!
- Execution
- Built-up
- Maximum power ESP kVA
- 715 kVA
- Maximum power ESP kW
- 572 kW
- Rated power PRP kVA
- 643 kVA
- Rated power PRP kW
- 515 kW
- Rated current
- 932 A
- Frequency
- 50 Hz
- Engine
- Baudouin
- Fuel type
- Diesel
- Fuel consumption 100% l/h
- 136.3 l/h
- Fuel tank
- 800 l
- Dimensions L x W x H
- 4500 x 1800 x 2410 mm
- Application
-
Business
Data Center
Health service
Industry - Type
- Stationary
- Weight
- 6150 kg